Standards and Classifications applicable to our iNTELECT™ switchboards are:


Standards


AS/NZS 3439.1
IEC 60439-1
BS EN 60439-1
Low Voltage Switchgear and Controlgear Assemblies
AS/NZS 2420 Fire Test Methods for insulation Material and Non-Metallic Enclosures for Electrical Equipment
AS/NZS 1939 Classification of Degree of Protection of Enclosures for Electrical Equipment
AS/NZS 3000 SAA Wiring Rules
AS/NZS 3947.4.1
IEC 947-4.1
Co-ordination of Short-Circuit Protective Devices

Classifications


General

Type tested low-voltage switchgear and controlgear assembly (TTA).


Type

Multi-cubicle type assembly. Indoor installation (or contained in an enclosure for outdoor installation). Stationary.


Construction

Degree of Protection  IP42 to IP54
Pollution Pollution degree 3
Clearance distances 20mm Min.
Creepage distances 29mm Min.

Electrical Characteristics

Rated operational voltage (Ue) 1000V max.
Rated insulation voltage (Ui) 1000V max.
Rated impulse withstand voltage (Uimp) 16kV
Rated current phase bars Up to 6000A
Rated current neutral bar Not less than 50% of the phase bars
Rated short-time withstand current (Icw) Phase bars 50kA at 1 sec
50kA at 3 secs
63kA at 1 sec
65kA at 1 sec
65kA at 3 secs
80kA at 1 sec
Rated short-time withstand current (Icw) neutral bars Not less than 60% of the short circuit rating of the phase bar.
Rated peak withstand current(Ipk) 105, 139, 143 and 176kA
Rated frequency 50-60Hz